BS 6231 CK 90°C

  • REACH
  • RoHS
  • CE
  • CPR Compliant
cable-preview
cable-pack-preview
cable-inner-preview

Application

High temperature, flame retardant cable designed for use in switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.

Standard

BS6231 Type CK.

Technical Data

Voltage Rating: 600 / 1000V

Temperature Rating : 90°C (105°C for 15,000 hours)

Minimum Bending Radius :

Cable diameter ≤ 8 mm: 4 x outer diameter.

Approx. diameter > 8 to 12 mm: 5 x outer diameter

Approx. diameter > 12 mm: 6 x outer diameter

Test Voltage: 4000V

Construction

Conductor: Conductor Class 5 flexible plain/metal coated stranded according to EN 60228 cl. 5.

Insulation: PVC (Polyvinyl Chloride) TI3 to BS EN 50363-3.

Properties

  • PVC self-extinguishing and flame retardant according to EN 60332-1-2.

Cabel Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink,
12 – grey.
By adding the suffix (in place of ‘c’) for the conductor type required:
0 = Annealed Bare Copper (ABC), 1 = Annealed Tinned Copper (ATC).

Part NumbersNominal Cross
Sectional Area
(Sq. mm)
Nominal Thickness
of Insulation
(mm)
Mean Overall Diameter
Approx. Cable
Weight
(kg/km)
Lower Limit (mm)Upper Limit (mm)
02060101xx3c0.50.82.43.011
02060102xx3c0.750.82.63.114
02060103xx3c10.82.73.316
02060104xx3c1.50.83.03.621
02060105xx3c2.50.83.44.132
02060106xx3c40.83.94.846
02060107xx3c60.84.45.364
02060108xx3c101.05.77.2109
02060109xx3c161.06.79.0166
02060110xx3c251.28.411.5256
02060111xx3c351.29.712.5352
02060112xx3c501.411.515.4501
02060113xx3c701.413.217.5692
02060114xx3c951.615.119.2914
02060115xx3c1201.616.721.21155
02060116xx3c1501.818.623.91441
02060117xx3c1852.020.625.91754
02060118xx3c2402.223.528.92305

Note :

  • These cable are also catered with compliance to AWM, UL 1015 and CSA C22.2 No. 210-11 as Trirated cable.
  • For current ratings refer table no. 8-1 & 8-2.