FIREX LS0H

  • REACH
  • RoHS
  • CE
  • CPR Compliant
cable-preview
cable-pack-preview
cable-inner-preview

HFFR (Halogen Free Flame Retardant) insulation 90°C | Non-Toxic & Non-Corrosive | Does not propagate flame & fire.

Application

These cables are ideal for domestic applications, conduit wiring and fixed, protected installations. Apart from residential and commercial properties, these cables are best suited for Auditoriums, Hospitals, Hotels, Schools, Stadiums and all constructions for Publicusage. These cables are ideal for use in environments where high-performance, reliability and safety is a norm.

Technical Data

Approvals: IS 17048 marked, FIA/TAC

Cable Code: XZ

Voltage Grade: Up to and including 1100V

Conductor: Strands of electrolytic annealed plain copper are multi-drawn for uniformity of resistance, dimension and flexibility.

Insulation: HFI-XL 90 Crosslinked (thermoset) halogen free flame retardant.

Colours: Green, Black, Red, Yellow, Blue, Grey, White

Marking: The cables are marked ‘FIREX LSOH’

Packing: 90 mtrs. Coils packed in protective cartons.

Properties

  • Temperature range : -15°C to +90°C
  • Max. short circuit temperature rating: 250°C
  • The insulation does not burn readily.
  • It does not melt and drip
  • Smoke is negligible, transparent, non-toxic
  • The victims trapped in fire do not suffocate and this facilitate fire fighting operations.
  • The cable has extended service life against the conventionally used cables.
  • The cable is also ozone resistant
  • Self-extinguishing and flame retardant according to IS 10810 P – 61
  • Anti-Rodent, Anti-Termite.

Cabel Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required
01 – Green, 02 – Black, 03 – Red, 04 – Blue, 05 – Yellow, 06 – Grey, 07 – White

Part NumberNominal Cross
Sectional Area
(sq. mm)
Nominal
Insulation Thickness (mm)
Number / Nominal Dia. of StrandsApprox. Overal Diameter (mm)Max.DC Conductor Resistance at 20°C
(Ω/km)
Current Rating (Amps)
CasingConcealed
01010101xx601.0*0.714/0.32.718.11917
01010102xx601.5*0.722/0.33.012.12421
01010103xx602.5*0.836/0.33.77.413729
01010104xx604.0**0.856/0.34.14.954133
01010105xx606.0**0.884/0.34.63.305343
  • *As per conductor class 2 of IS 8130
  • ** As per conductor class 5 of IS 8130

Test Parameters for Assessment of Halogen

TestTest MethodValues
pHIS 17048≥ 4.3
ConductivityIS 17048≤ 10 μs/mm
Chlorine and bromine expressed as content of HCLIS 10810 P – 59≤ 0.5 %
Presence of fluorineIS 17048≤ 0.1 %