SINGLE CORE FIRE RESISTANT

  • REACH
  • RoHS
  • CE
  • CPR Compliant
cable-preview
cable-pack-preview
cable-inner-preview

Application

These cables are designed for installations in trunking and conduits where a fire situation may pose a major hazard. Circuit integrity is maintained and to achieve optimum performance such cables should be installed in metal conduits.

Standard

Adapted to EN 50525-3-41

Technical Data

Voltage Rating: 450 / 750 V

Operating Temperature: -20°C to + 90°C (the cable should not be flexed when the temperature is below 0°C)

Minimum Bending Radius: 8 x Overall diameter

Cable Construction

Conductor: Stranded plain annealed copper conductor to BS EN 60228, class 2.

Insulation: Mica (fire resistant) tape covered by an extruded layer of cross – linked low smoke zero halogen (LS0H), insulating compound

*Sheathed version also available. Details available on request.

Properties

Circuit Integrity for installation in metal conduits: BS 6387 categories C, W & Z (when applied to a single cable) Exceeds IEC 60331 – 3 hours at 750°C – when the test temperature was increased to 950°C, equivalent to BS 6387 category C

Acid Gas Emission: IEC 60754-1, BS EN 50267-2-1

Smoke Emission: IEC 61034, BS EN 50268

Flame Propagation: EN 60332-1, EN 60332-3, BS EN 50265, BS EN 50266

Cable Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the insulation colour required :
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green / yellow, 09 – brown, 12 – grey.

Part NumberNominal Cross
Sectional Area (Sq. mm)
Insulation Thickness
(mm)
Max. Overall
Diameter (mm)
Approx. Cable
Weight (kg/km)
10040101xx601.50.73.832
10040102xx602.50.84.543
10040103xx6040.8555
10040104xx6060.85.585
10040105xx601017146
10040106xx601618198
10040107xx60251.29.7320
10040108xx60351.210.8410
10040109xx60501.413.3549
10040110xx60701.415.1770
10040111xx60951.617.51140
10040112xx601201.619.21425
10040113xx601501.821.21720
10040114xx60185223.62155